How big is the air compressor room generally to be built, and what aspects should be paid attention to?

作者: Bolet air compressor 时间:2020.06.15 Number of page views: 7791

Many enterprises need to use a batch of air compressors for production reasons, so it is necessary to build a special factory for these air compressors and post-processing equipment。那么Air compressor roomHow big does it usually take to build?What aspects should we pay attention to?

Here we want to make it clear in advance: the construction of the air compressor room depends on how big the machine you want to use,How many machines and the associated number of post-processing equipment!For example, a single 30KW screw air compressor needs to be equipped with a storage tank, a cooling and drying machine and three filters,These cover an area of about 5 square meters,The height is generally not more than 4 meters。


The following isAtlas compressorThe relevant content of the air compressor room building compiled by Xiaobian:

1. The selection of the air compressor room should ensure that the maintenance of the air compressor is convenient in the future and avoid the abnormal operation of the air compressor due to the unsatisfactory environment。The appropriate installation site is the prerequisite for the correct use of the air compressor system。

2. The air compressor room requires low relative humidity, less dust, clean air and good ventilation。

If the ambient temperature is too high (greater than 45 ° C), it is recommended to take cooling measures (such as avoiding direct sunlight, opening doors and Windows) to avoid unnecessary high-temperature shutdown。If the ambient temperature is low (less than 0 ° C), the freezing point temperature of the lubricating oil must be controlled above the ambient temperature。

If the factory environment is poor and there is much dust, a ventilation duct should be installed to direct the intake end to a place where the air is relatively clean。The installation of the pipe must be easy to disassemble and assemble for maintenance, and the installation size shall refer to the external size of the air compressor。

3. The space around the air compressor must be reserved enough for other parts to enter and exit, and the distance between the air compressor and the wall must be at least 1500mm or more。Lifting equipment is preferred。

4. The installation site of the air compressor room requires good lighting and sufficient lighting to facilitate operation and maintenance。

5. The space distance between the air compressor and the top of the air compressor room is more than 1500mm。

Previous post:What is the volume flow of air compressor?
Next post:Atlas GA160 machine can not start, what is the reason for the empty filter oil?